NOTE: These instructions cover abandoning all 3-inch and 4 inch core holes.

Step 1 Locate poke-thru unit or core hole that needs

to be sealed with an abandonment plug.

Step 2 Remove slide holder assembly and the internal gasket.

Disconnect power and communications devices and
remove flange.

Step 3 Remove poke-thru unit from hole.

Step 4 Push in proper abandonment plug.

For 3" core hole, use ABPLUG3
For 4" core hole, use ABPLUG4

Step 5 Installation complete.

NOTE: Abandonment Plugs are required to maintain the fire rating of the floor assembly when ever a poke-thru fitting is not used.

The abandonment plugs in these instructions are shown in the UL Fire Resistance Directory.

ABPLUG3 & ABPLUG4 INSTALLATION: