Electrical wiring chart – Legrand RC4KTCBK User Manual

Page 2

Advertising
background image

COMPLETE ASSEMBLY:

Step 6. Cat. Nos. RC4ATC or RC4ARTTC.

Step 7. Wire the power circuit. See wiring diagram.

Wire the Poke-Thru device.
(Can be completed above floor.)
Refer to wiring schematic in Step 8.

Step 8. Wiring Diagram. Connect receptacle

Step 9. If circuit is connected to an isolated ground

leads to branch circuit conductors

apply IG icon on receptacle slide as shown.

as required.

WARNING: Ground wire from junction box must be connected

to SYSTEM GROUND.

CAUTION: Receptacle mounting means not grounded.

NOTE: The orange triangle shall only be placed on devices

Grounding wire connection required. For isolated

that are wired for isolated ground. See NEC 250-146(d).

ground wiring; connect ground leads to a separate
isolated grounding conductor. See NEC 250-146(d).

2

Two #6-32 Slide Cover
Mounting Screws

NOTE: Gasket and gasket

support must be
removed before wiring
data connections.

Gasket

Gasket Support

Branch Circuit Conductors

Electrical and Communication Cables May be

Connected to Unit Prior to or After Activation.

Junction Box
24.5 cu. in. [400cm

3

]

Circuit “B”

Circuit “A”

Circuit “A”

Circuit “B”

Line

Black

Red

Neutral

White

White w/Blue Stripe

Ground

Green

Green w/Yellow Stripe

Electrical Wiring Chart