Step 8. If circuit is connected to an isolated ground, apply IG icon on receptacle slide as shown.

NOTE: The orange triangle shall only be placed on devices that are wired for isolated ground. See NEC 250-146(d).

Step 9. Wire and snap the communication jacks into the adapters as shown.

NOTE: To maintain UL Fire Classification, all communication modules or blank inserts (factory or customer supplied) must be UL Listed

communication circuit accessories, and must fit securely in the supplied communication brackets with no visible openings between
the module and bracket. Supplied foam plugs must be used when passing cables through the communication openings.

Step 10. For cable pass-through or empty communication port, install foam block in keystone adapter.

Pass cable through adapter adjacent to foam plug. Close off non-utilized Ortronics adapters with
plastic TracJack

blank.

CAUTION: Empty communication ports must be closed off with foam blocks or TracJack blanks to maintain fire classification.

Keystone

Foam Plug

TracJack

Blank

TracJack Adapter

Keystone Adapter

Ortronics

Avaya