Legrand 2000 Series Aluminum Plugmold Multioutlet System User Manual

Page 4

Advertising
background image

AL2000B Base

To attach AL2000B base sections to mounting surface, drill
9/32" holes in the base (approx. 48" o.c.). Fasten base with
#8 flathead head screws.

AL2001 Coupling

At AL2000B base section butt joints, slide AL2001 Coupling
into first base section mount next base to surface. Center
coupling on joints. Tighten locking screws.

AL2009 Ground Clamp

Position AL 2009 Ground Clamp into rib in AL2000B raceway
base. Tighten locking screw. Attach ground wire using brass
cup washer and green hex nut to ground lug.

AL2051H Box Adapter

Use for feed raceway from existing wall outlet box. To install,
attach adapter to outlet box with two screws. This system is
designed with capacity for additional feed or circuitry conductors.

48"

[1219mm]

WIREMOLD

U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251
Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
1-800-723-5175 • FAX 905-738-9721

1 009 949 0211

© Copyright 2011 Legrand/Wiremold All Rights Reserved

Advertising
This manual is related to the following products: