2.14 @AA
Description: Read Digital Input/Output Status
Command: @AA[CHK](cr)
@
Delimiter character
AA
Address of reading module (00 to FF)
Response:
Valid Command:
>(Data)[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no response.
>
Delimiter for valid Command
?
Delimiter for invalid Command
AA
Address of response module(00 to FF)
(Data)
Read DIO status (Ref. Sec. 1.9)
Example:
Command: @01
Receive: >0F00
Read Address 01 DIO status, return 0F00.