Operation, 7 stopping procedures, 8 emergency stop – MMD Equipment 40S-8B1 User Manual

Page 38: 9 air bleeding

Advertising
background image

4. Operation

4-17

4.7 Stopping Procedures

<Procedure>

①

Switch “OFF” the breaker on the operation panel of the generator.

②

After performing cooling down operation about 5 minutes, place the starter switch to the“STOP”

position to stop the engine.

③

While the machine is kept unused, keep the operation selector switch placed to the “OFF”position.

4.8 Emergency Stop



The Emergency Stop button should be used only for emergency stop.



Regularly check the operating performance.



If it is necessary to stop the generator for emergency,
press the Emergency Stop button

.











To reset the button, turn the button head in the
direction of the arrow. If it is not reset, the machine
cannot restart to operate

.

4.9 Air Bleeding

Should the machine stop due to the shortage of fuel, perform the air bleeding operation according to
the following procedures.

<Procedure>

①

Place the operation selector switch to the “MANUAL” position.

②

Place the starter switch to “RUN” position to put electromagnetic pump into operating conditions.

③

Air bleeding will be completed within 20-30 seconds.

④

Place the operation mode selection switch to “LOW” position and start engine.

⑤

Keep warming up operation for 3 minutes after engine has started.

⑥

Then place the operation mode selection switch to “HIGH” position and raise engine speed up to the
rated speed (RPM). Thereafter, repeat mode selection operation “LOW”⇔“HIGH”several times.

H980178

H980179