A = clearance to the termination frame above grade, veranda, porch, deck,

or balcony [30 inches (75 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened [30

inches (75 cm) minimum for appliances.

C = clearance to bottom of window that may be opened horizontally [36

inches (92 cm) minimum for appliances.

D = no clearance to permanently closed window when installed with approved

glass penetration termination

E = clearance to permanently closed window [30 inches 75 cm recommended

to prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination

within a horizontal distance of [30 inches 75 cm] from the centreline of

the termination [30 inches (75 cm) minimum]

G = c l e a r a n c e t o u n v e n t i l a t e d s o f f i t [ 3 0 i n c h e s

( 7 5 c m ) m i n i m u m t o n o n - c o m b u s t i b l e s ]

[30 inches (75 cm) minimum to combustibles]

H = clearance to outside corner [30 inches (75 cm) minimum]
I = clearance to inside corner [30 inches (75 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the United

States] [*6 feet (1.8 m) minimum in Canada]

L = clearance to non-mechanical air supply inlet to building or the combustion

air inlet to any other appliance [16 inches (41 cm) minimum for appliances

≤100 000 BTU/H (30kW)]

M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]

N =

†

clearance above paved sidewalk or a paved driveway located on public

property [*7 feet (2.1 m) minimum]

P = clearance under veranda, porch, deck, or balcony [30 inches (75

cm) minimum

‡

to non-combustibles] [30 inches (75 cm) minimum

‡

to

combustibles]

Q = clearance above a roof [18 inches (46 cm) minimum]
R = clearance to adjacent walls and neighboring buildings [30 inches (75

cm) minimum]

S = clearance from corner in recessed location [30 inches (75 cm) minimum]
T = maximum depth in recessed location [48 inches (122 cm) minimum]
U = minimum width for back wall of recessed location [60 inches (150 cm)

minimum]

V = minimum horizontal clearance between the frames of two terminations

that are level, (see applicable Detail).

W = horizontal clearance between the frames of two terminations that are

not level. [30 inches (75 cm) minimum]

†

a vent shall not terminate directly above a sidewalk or paved driveway

which is located between two single family dwellings and serves both

dwellings

‡

only permitted if veranda, porch, deck, or balcony has an open side that

is equal to or greater than the depth of the enclosed area

*

as specified in CGA B149 Installation Codes. Note: local Codes or

Regulations may require different clearance.

V

Vertical Detail

Horizontal

Detail