Appendix a - termination locations, Page 4 epvrr residential power vent system – Montigo EPVRR User Manual

Page 4

Advertising
background image

Page 4

EPVRR Residential Power Vent System

Part No. XG1306 - 022813

Appendix A - Termination Locations

A = clearance to the termination frame above grade, veranda, porch, deck, or balcony

[30 inches (75 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened [30 inches (75

cm) minimum for appliances.

C = clearance to bottom of window that may be opened horizontally [36 inches (92

cm) minimum for appliances.

D = no clearance to permanently closed window when installed with approved glass

penetration termination

E = clearance to permanently closed window [30 inches 75 cm recommended to

prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination within a horizontal

distance of [30 inches 75 cm] from the centreline of the termination [30 inches (75

cm) minimum]

G = clearance to unventilated soffit [30 inches (75 cm) minimum to non-combustibles]

[30 inches (75 cm) minimum to combustibles]

H = clearance to outside corner [30 inches (75 cm) minimum]
I = clearance to inside corner [30 inches (75 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the United States]

[*6 feet (1.8 m) minimum in Canada]

L = clearance to non-mechanical air supply inlet to building or the combustion air inlet

to any other appliance [16 inches (41 cm) minimum for appliances ≤100 000 BTU/H

(30kW)]

M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]

N =

†

clearance above paved sidewalk or a paved driveway located on public property

[*7 feet (2.1 m) minimum]

P = clearance under veranda, porch, deck, or balcony [30 inches (75 cm) minimum

‡

to non-combustibles] [30 inches (75 cm) minimum

‡

to combustibles]

Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighboring buildings [30 inches (75 cm) mini-

mum]

S = clearance from corner in recessed location [30 inches (75 cm) minimum]
T = maximum depth in recessed location [48 inches (122 cm) minimum]
U = minimum width for back wall of recessed location [60 inches (150 cm) minimum]
V = [30 inches (75 cm) minimum] horizontal clearance between the frames of two

terminations that are level.

W = horizontal clearance between the frames of two terminations that are not level.

[30 inches (75 cm) minimum]

†

a vent shall not terminate directly above a sidewalk or paved driveway which is

located between two single family dwellings and serves both dwellings

‡

only permitted if veranda, porch, deck, or balcony has an open side that is equal

to or greater than the depth of the enclosed area

*

as specified in CGA B149 Installation Codes. Note: local Codes or Regulations

may require different clearance.

18”

30”Min.

30”Min.

18”
Min.

Front View

[V]

Advertising