Warning, Installation, Linear power vent - horizontal vent – Montigo LDVPV47 User Manual

Page 7: Ldvpv47 linear power vent system

Advertising
background image

Page 7

LDVPV47 Linear Power Vent System

XG0750 -112911

Installation

Section:

Montigo is not responsible for any water damage that may occur from installing

equipment other than what is specified in this document.

WARNING

Linear Power Vent - Horizontal Vent

Multi-elbow installations are possible up to a maximum one-hundred feet

(100'-0"), with three (3) 90° elbows. Minimum vent run from Fireplace

to Power Vent must be two feet, (2'-0"). Maximum allowable vent run

must be reduced by Ten feet (10'-0") for every 90° elbow added. With

a snorkel Termination, reduce the total vent run by an additional twenty

feet (20'-0"). Figure's 3a and 3b.

Example A. Vertical Mounting with horizontal Vent Run

Figure 3a. Vertical Mounting for the Linear Power Venter

2’-0 ”

MIN

Vertical Installed
Linear Power Vent

Horizontal Run Flex Pipe

Vertical
Flex Pipe

90deg
Elbow

90deg
Elbow

90deg
Elbow

Termination

Snorkel
Termination

Important:

Maximum Vent Run not to exceed

One-Hundred feet (100’-0”) feet.

Figure 3b. Horizontal Vent for the Linear Power Vent
Termination Snorkel

Example B. Horizontal Mounting with horizontal Vent Run

Horizontal Installed
Linear Power Vent

Horizontal Run Flex Pipe

Vertical
Flex Pipe

90deg
Elbow

90deg
Elbow

90deg
Elbow

Termination

Snorkel
Termination

Important:

Maximum Vent Run not to exceed

One-Hundred feet (100’-0”) feet.

Available
Option

Linear Power Vent - Vertical Vent
Multi-elbow installations are possible up to a maximum one-hundred

thirty feet (130'-0"), with three (3) 90° elbows. Minimum vent run from

Fireplace to Power Vent must be two feet, (2'-0"). Maximum allowable

vent run must be reduced by Ten feet (10'-0") for every 90° elbow added.

Figure's 4a and 4b.

Figure 4a. Vertical Vent for the Linear Power Venter

Example A. Vertical Mounting with Vertical Vent Run

2’-0 ”
MIN

Vertical Installed
Linear Power Vent

Vertical
Flex Pipe

90deg
Elbow

90deg
Elbow

90deg
Elbow

90deg
Elbow

Termination

Important:

Maximum Vent Run not to exceed

One-Hundred Thirty (130’-0”) feet.

2’-0 ”
MIN

Example B. Vertical Mounting with Vertical Vent Run

Figure 4b. VerticaI Linear Power Vent with Vertical Vent Run.

Vertical Installed
Linear Power Vent

Vertical
Flex Pipe

90deg
Elbow

90deg
Elbow

90deg
Elbow

90deg
Elbow

Important:

Maximum Vent Run not to exceed

One-Hundred Thirty (130’-0”) feet.

Termination

2’-0 ”

MIN