f i r e f e a t u r e

EDVPV47-58 Power Vent System

Part No. XG0700 - 090909

Appendix A - Termination Locations

A = clearance to the termination frame above grade, veranda, porch, deck, or

balcony [16 inches (41 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened [16

inches (41 cm) minimum for appliances ≤100 000 BTU/H (30kW)]

C = clearance to bottom of window that may be opened horizontally [36 inches

(92 cm) minimum for appliances ≤100 000 BTU/H (30kW)]

D = no clearance to permanently closed window when installed with approved

glass penetration termination

E = clearance to permanently closed window [16 inches 41 cm recommended

to prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination within a

horizontal distance of 2 feet (61 cm) from the centreline of the termination

[22 inches (56 cm) minimum]

G = clearance to unventilated soffit [16 inches (41 cm) minimum to non-combustibles]

[22 inches (56 cm) minimum to combustibles]

H = clearance to outside corner [9 inches (23 cm) minimum]
I = clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the United

States] [*6 feet (1.8 m) minimum in Canada]

L = clearance to non-mechanical air supply inlet to building or the combustion

air inlet to any other appliance [16 inches (41 cm) minimum for appliances

≤

100 000 BTU/H (30kW)]

M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]

N =

†

clearance above paved sidewalk or a paved driveway located on public

property [*7 feet (2.1 m) minimum]

P = c l e a r a n c e u n d e r v e r a n d a , p o r c h , d e c k , o r b a l c o n y

[ 1 6 i n c h e s ( 4 1 c m ) m i n i m u m

‡

t o n o n - c o m b u s t i b l e s ]

[22 inches (56 cm) minimum

‡

to combustibles]

Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighboring buildings

[18 inches (46 cm) minimum]

S = c l e a r a n c e f r o m c o r n e r i n r e c e s s e d l o c a t i o n

[12 inches (31 cm) minimum]

T = m a x i m u m d e p t h i n r e c e s s e d l o c a t i o n

[48 inches (122 cm) minimum]

U = m i n i m u m w i d t h f o r b a c k w a l l o f r e c e s s e d l o c a t i o n

[24 inches (61 cm) minimum]

V = no horizontal clearance between the frames of two terminations that are

level.

W = horizontal clearance between the frames of two terminations that are not

level. [36 inches (92 cm) minimum]

†

a vent shall not terminate directly above a sidewalk or paved driveway which

is located between two single family dwellings and serves both dwellings

‡

only permitted if veranda, porch, deck, or balcony has an open side that is

equal to or greater than the depth of the enclosed area

* as specified in CGA B149 Installation Codes. Note: local Codes or Regula-

tions may require different clearance.