Repair Section

34

(4) Inspection of drain tanks (optional)

• Make sure tank is fully drained.

< NOTE >

If the fan mode control DIP switch is set to the stop position, the entire unit (including fan

operation) turns off.

The following pages (page 34 to 42) are self-diagnostic codes and troubleshooting information.

Detailed information is contained in the OPERATION MANUAL supplied with the unit.

7.2 Self-Diagnostic Codes

• Self-diagnostic codes are displayed on the control board under the following conditions and

clear method is as follows.

LCD Display

Description

Condition

Reset/Remedy

Drain tanks is full

When the drain tanks (optional) is

filled with drain water.

(“TANK FL” LED flashes and signal

output (J106) turns on.)

1) Drain away.

(LCD indicates “TANK”)

2) Press ON/OFF button.

Condensate pump

problem

When condensate pump is

damaged or broken.

(J8 input of relay board turns to

open and signal output (J106) turns

on.)

1) Fix the condensate pump.

2) Reset the system.

To RESET: Press ON/OFF and

HI/LO buttons on the control box

simultaneously for 5 sec.

Defect (short or open)

of room thermistor

When room thermistor (connecting

to J101) becomes short or open.

(Signal output (J106) turns on.)

Disconnect and reconnect the

room thermistor.

If it doesn’t work, then change it.