3-5-9. Changing battery quantity (number)
The default battery (12V) quantity of this UPS system is 20 (for one series), but 18, 19 could also be applied in
this system. However, before changing the battery quantity, the UPS should be fully shutdown and the cabinet
cover should be removed, and the jumpers on the control board should be re-set as below table:

Note:1 = insert with jumper; 0 = no jumper; x = these pins are for other functions.

NOTE: This operation should be done by professional technicians, please contact the dealer for support

3-6. Parallel UPS Operation

For parallel UPS operation, please contact your dealer for more professional support.

Battery Number

(one series)

JP1 on control board

pin1 & pin2

pin3 & pin4

Pin5 & pin6

pin7 & pin8

18

X

X

0

0

19

X

X

1

0

20

X

X

1

1