ONICON D-100 Dualnet User Manual

Page 12

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 12

1.6 BACnet MS/TP BAUD RATE, BIASING & TERMINATION

1.6.1 Baud Rate

Every ONICON D-100 is individually programmed at the factory with application specific

data provided by the customer during the process of ordering the meter, and this normally

includes the Baud rate setting. If the Baud rate was provided, the meter will be configured

to operate at the specified rate. The standard Baud rate settings are 9600, 19200, 38400 and

76800 Baud.

The Baud rate setting is selected using dipswitch SW4, positions 1-3. The photo and table

below show the Baud rate dipswitch settings.

Baud Rate

1

2

3

4

9600

On

On

On

Off

19200

Off

Off

Off

On

38400

On

On

Off

On

* 76800

On

Off

On

On

115200

Off

On

On

On

Baud Rate Dip Switches

ON

(Circuit board shown upside down for clarity.)

* Not supported on MODBUS RS-485

Advertising