Zoning Design Guide

System Manager

•

24 VAC Supply Voltage (6 VA)
and Communications Loop
Use Prefabricated Modular Cable

VAV/Zone Controller

•

24 VAC Supply Voltage (6 VA)
and Communications Loop
Use Prefabricated Modular Cable

•

Modular Room Sensor
Use Prefabricated Modular Cable

Sensor Wiring
Orion temperature sensors utilize a type III thermistor
element that is one of the most commonly used sensors
in the building controls industry. The sensor wire should
be a minimum of 24 gauge however larger wire such as
18 gauge is commonly used. The exception to this is
the VAV/Zone Controller utilizes a Modular Room Sen-
sor which is connected with a prefabricated modular
cable.

Conventional thermostat cable is acceptable in most
commercial and institutional installations. In some in-
stallations which have the potential for high electrical

noise, such as broadcast facilities (radio, TV, etc.), heavy
industrial (machinery, welding equipment, etc.), and
medical (x-ray, scanning, etc.), it is advisable to use
shielded cable on sensors which are located in or close
to these environments. The same cable used for the com-
munication bus can be used in these situations.

Sensor requirements are:

•

Supply Air Sensor
(2) Conductors 24 gauge minimum

•

Return Sensor
(2) Conductors 24 gauge minimum

•

Outside Air Sensor
(2) Conductors 24 gauge minimum

•

Standard Room Sensor (HVAC Unit
Controllers Only)
(2) Conductors 24 gauge minimum
(3) Conductors if using optional slide
adjust

•

Modular Room Sensor (used with VAV/
Zone Controllers Only)
Use Prefabricated Modular Cable