Installation inside buildings

■

Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(figure 7)

.

■

Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses (figure 7)

■

Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes
placed opposite each other
(figure 7)

.

Minimum clearances

Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.

ATY 261 DC AT

ATY 351 DC AT

A

100 mm

100 mm

B

700 mm

700 mm

C

400 mm

400 mm

D

100 mm

100 mm

E

300 mm

300 mm

■

Comply with any regulations
and conditions affecting the
structure of the building.
If necessary, fit acoustic
installation.