Remko vrs, Troubleshooting – REMKO VRS Series User Manual

Page 18

Advertising
background image

18

REMKO VRS

troubleshooting

Possible causes:

■

The heaters could not cool

down because the power supply
was interrupted.
A brief interruption of the pow-
er supply can also cause the STB
to operate.

■

The temperature of the air
being blown out is too high due
to incorrectly installed chimney
ducts or adjusted grilles.

■

The fan was overloaded and the

thermal overcurrent relay of the
400V type heater or thermal
contacts in the fan motor of
the 230V type heater have
operated.

■

The V-belt for the fan drive is

loose or faulty.

■

The air inlet or outlet is not free.

■

Check the temperature control

thermostat (TR) for correct
functioning and adjustment.

■

Check the temperature monitor

(TW) for correct functioning
and adjustment.

the burner does not start

■

Check the oil filter for clogging.

Replace clogged filter(s).

■

Check that the shut-off valve

on the oil filter is open.

■

Check the fuel tank for suffi -

or suffi-

cient fuel.

■

Check the fuel and filter for

paraffin separation.
Paraffin separation can occur
already below 5°C.

■

Check the oil hoses for damage

and leaks.
Air may also be sucked in!

■

Check the safety temperature

limiter (STB).

■

Check the temperature monitor

(TW).

the heater does not start

■

Check the local mains supply

connection.

■

Check the fuses in the control

box.
(Only 400V three-phase type)

■

Set the switch to the „I“ or

Heat position.

■

Check that the „Burner“ indi-

cator light on the control box
(only 400V type) is illuminated.

■

Check the thermostat connec-

tion or room thermostat cable.

■

Check the room thermostat

setting.
The temperature set must be
higher than the existing room
temperature.

■

Check whether the safety tem-

perature limiter (STB) may have
operated.

AttENtION

Prior to carrying out main-
tenance or repairs, the unit
must be disconnected from the
mains supply.

AttENtION

Prior to releasing a safety
device, the cause of operation
must be located and
eliminated.

NOtE

Safety devices must not be
overridden or blocked during
heater operation!