Unit assembly – REMKO PWW 6000 User Manual

Page 5

Advertising
background image

5

Unit Assembly


Brackets

Brackets for wall and ceiling assembly (2 per unit) are
inserted into the openings at the back of the unit and at-
tached with the supplied screws.
Components that are attached directly to the units,
such as mixed-air boxes or filter boxes, are equipped
with a bracket adapter.
When using customer-installed bracket constructions,
the minimum distance to the wall (dimension "e") must
be observed!
KO bracket

For wall and ceiling assembly

Cu / Al heat-exchangers

The heat-exchangers are made of copper pipes with alu-
minium plate fins pressed onto the outside. The plate fin
package is surrounded by a galvanized, zinc-plated steel
frame.
The collector and the distributor are made of steel.
Please observe the following for the heat-exchangers:

◊

The heating medium connection is made via
threaded connectors.

◊

The maximum operating temperature is 130 °C.

◊

The maximum operating pressure is 16 bar.

◊

The heat-exchangers are not suitable for operation
with steam or thermal oil.

Connection to the heating system

◊

The REMKO PWW is to be connected by the cus-
tomer via the shut-off valve, automatic dehumidifier
and screws in the supply and return lines.
Use compensators if necessary.

◊

It does not matter which side is connected.

Right or left.

◊

The units operate on the principle of counter-current.

◊

The water (supply line) usually comes in at the bot-
tom. The water usually goes out (return line) at the
top.

Draining in case of frost

It is not possible to statically drain the heat-exchanger
completely. The heat-exchanger can only be com-
pletely drained when compressed air is used.

Drainage

Dehumidification

Frost protection thermostat

Screws

Incoming air

Outgoing air

Incoming water

Outgoing water

PWW

Dimension

a b c d

6030-3 / 4

562

432

512

155

270

6050-3 / 4

642

507

592

192

270

6080-3 / 4

802

622

752

250

270

6100-3 / 4

882

732

832

305

340

e

The brackets must be current-free and screwed on
to the unit and the wall/ceiling.

*

◊

After assembly, the heat-exchanger must be care-
fully dehumidified.

Air pockets in the register reduce the unit perform-
ance.

◊

You can find the thread sizes of the heat register

in

the technical data.

When the fan is idle, the heating medium supply
must be interrupted.

*

Important information about frost protection!

To prevent frost damage, a frost protection mechanism
must be attached for temperatures below 0 °C.
There may not be any water in the heat-exchanger for
systems taken out of operation in rooms susceptible to
frost. The remaining water must be blown out with com-
pressed air.
If this is not possible, the heating medium (water) must
be mixed with a suitable anti-freeze.

No guarantee claims can be made for frost damage
on the heat-exchanger!

*

KO

e

c

a

b

d

d

Ø

12.5