Type C13 horizontal / coaxial

L1 + L2 maximum duct length

without endpieces

Ø 80

Ø 100

Model

Metres

GPM15

10 + 10

GPM25

10 + 10

GPM35

10 + 10

GPM55

4.5 + 4.5

GPM 75

4 + 4

Type C33 vertical / coaxial

L1 + L2 maximum duct length

without endpieces

Ø 80

Ø 100

Model

Metres

GPM15

11 + 11

GPM25

11 + 11

GPM35

11 + 11

GPM55

4.5 + 4.5

GPM 75

4 + 4

Gas fireplace type C

Room-air-independent combustion
system.
The combustion cycle is compact
compared to the environment in
which it is installed.
The combustion air is fed from
outside.
The ductwork runs horizontally
through the outside wall or
vertically through the roof.

L1

L2

Installation

height

Schematic

side view

2.5 - 3.5 m

L1

L2

Installation height

2.5 - 3.5 m

Schematic

side view

L1

L2

Installation height

2.5 - 3.5 m

Schematic
front view

In this version the position of
the connections to the unit
must be changed, meaning
they must be repositioned
from behind to above.

This

variant is executed at the

factory and must be indicated

when ordering.

NOTE

NOTE

The installation of the exhaust
gas routeing through the
outside wall must correspond
to the regulations of DVGW -
TRGI and TRF as a basic rule
and must be approved by the
responsible district master
sweep.

TYPE C33

Room-air-independent combustion
system.
Exhaust/ and combustion air are
led through an LAS endpiece
through the roof.

TYPE C13

Room-air-independent combustion
system.
Exhaust/ and combustion air are
led through an LAS endpiece
through the outside wall.