REMKO CMF / CMT

■

The outdoor- and the indoor
modules are connected with
two copper pipes of refrigerator
quality having the dimensions
“ and “ (REMKO special
accessory).

■

Observe the permitted bending
radius for the refrigerant pipes
during installation in order to
prevent kinks. Never bend a
pipe twice in the same place in
order to prevent embrittlement
or crack formation.

■

Assure suitable fastening and
insulation when laying the
refrigerant pipes.

■

The copper pipes are to be
flared to make the connections
to the modules. In doing so,
check that the flare has the
correct shape and suitable
union nuts. (Figs. 6 - 8).

Connection of refrigerant lines

Connection to the unit

■

Remove the cover panel from
the outdoor module. It may be
necessary to remove the pre-
cut bushings.

■

Take off the factory-fitted
protective caps. You can use
the union nuts for additional
mounting. Make sure to slide
the union nuts onto the pipe
before it is flared.

■

Make connections to the device
by hand initially, in order to
ensure a good fit. Later, tighten
the joints with two open-end
wrenches Use one wrench to
resist

the rotation of the other

(Fig. 9).

Flanging tool

7 Flanging the refrigerant line

Refrigerant line

Deburrer

6 Deburring the refrigerant line

Copper piping

Outside diameter

Flare

dimensions ø A

3/8” or 9.52 mm

12.8 - 13.2 mm

5/8” or 15.88 mm

19.3 - 19.7 mm

Tighten 1st Spanner

Counter
2nd Spanner

9 Tighten fittings

Tightening

torque

“: 32-40 Nm
“: 65-75 Nm

■

Special measures need not be
taken for the return of the com-
pressor oil.

8 Correct flange shape

■

The installed refrigerant pipes,
including the flare connections,
must be provided with suitable
insulation.


Use only tools which are
approved for use in an HVAC
environment.
(z. B.: bending
pliers, pipe/tubing cutters, de-
burrers and flaring tools). Do
not cut refrigerant pipes with a
saw.

NOTE


Outdoor modules may be
delivered with nuts suitable for
joining flanges.

NOTE

All work must be carried out
in a way that prevents dirt,
particles, water etc. from
entering, refrigerant lines!

!

CAUTION