Appendix A: Modbus Communication
User Guide: LD5000
76 970.484.6510
www.rletech.com
A-6.4 Network Display (Trace)
Type ND<CR> from the RS-232 configuration port to display the RS-485 traffic.
A-6.5 Modbus Display (Trace)
Type MT<CR> from the RS-232 configuration port to display the Modbus packets.
MT
Modbus trace/display is on <press any key to turn
off!>
<LD5000>
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ND
ok
RS485 Monitor On <press any key to turn off!>
<LD5000>
{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}