Remote Condenser Location - Limits

Use the following for planning the placement of the

condenser relative to the ice machine

Location Limits - condenser location must not exceed

ANY of the following limits:

• Maximum rise from the ice machine to the

condenser is 35 physical feet

• Maximum drop from the ice machine to the

condenser is 15 physical feet

• Physical line set maximum length is 100 feet.

• Calculated line set length maximum is 150.

Calculation Formula:

• Drop = dd x 6.6 (dd = distance in feet)

• Rise = rd x 1.7 (rd = distance in feet)

• Horizontal Run = hd x 1 (hd = distance in feet)

• Calculation: Drop(s) + Rise(s) + Horizontal

• Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these requirements

must receive prior written authorization from

Scotsman to maintain warranty.

Do NOT:

• Route a line set that rises, then falls, then rises.

• Route a line set that falls, then rises, then falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would be

acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and

then 100 feet away horizontally. 35 x 1.7 = 59.5.

59.5 +100 = 159.5. 159.5 is greater than the 150

maximum and is NOT acceptable.

Operating a machine with an unacceptable

configuration is misuse and will void the warranty.

22

.8

7"

17

.15

"

40.35"

rd Max 35 feet

dd Max 15 feet

hd

Remote Condenser located

above ice machine.

Remote Condenser located

below ice machine.

Condenser Distance &

Location Schematic