Remote Condenser Location

Use the following for planning the placement of the
condenser relative to the ice machine

Location Limits - condenser location must not
exceed ANY of the following limits:

•

Maximum rise from the ice machine to the
condenser is 35 physical feet

•

Maximum drop from the ice machine to the
condenser is 15 physical feet

•

Physical line set maximum length is 100 feet.

•

Calculated line set length maximum is 150.

Calculation Formula:

•

Drop = dd x 6.6 (dd = distance in feet)

•

Rise = rd x 1.7 (rd = distance in feet)

•

Horizontal Run = hd x 1 (hd = distance in
feet)

•

Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.

Do NOT:

•

Route a line set that rises, then falls, then
rises.

•

Route a line set that falls, then rises, then
falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and
then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150
maximum and is NOT acceptable.

October 2010

Page 8

C2648
Remote Condenser Models - User Manual

22.87"

17.15"

40.35"

dd

hd

rd

Remote Condenser Located

ABOVE Ice Machine

Remote Condenser Located

BELOW Ice Machine

Condenser Distance &

Location Schematic