CME506R, 656R, 806R: AutoIQ Cubers

January 2000

Page 6

Remote Condenser Location

Use the following for planning the placement of the

condenser relative to the ice machine
Location Limits - condenser location must not

exceed ANY of the following limits:

•

Maximum rise from the ice machine to the

condenser is 35 physical feet

•

Maximum drop from the ice machine to the

condenser is 15 physical feet

•

Physical line set maximum length is 100

feet.

•

Calculated line set length maximum is 150.

Calculation Formula:

•

Drop = dd x 6.6 (dd = distance in feet)

•

Rise = rd x 1.7 (rd = distance in feet)

•

Horizontal Run = hd x 1 (hd = distance in

feet)

•

Calculation: Drop(s) + Rise(s) + Horizontal

Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these

requirements must receive prior written

authorization from Scotsman.
Do NOT:

•

Route a line set that rises, then falls, then

rises.

•

Route a line set that falls, then rises, then

falls.

Calculation Example 1:
The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would

be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and

then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is

greater than the 150 maximum and is NOT

acceptable.

22.87"

17.15"

40.35"

hd

rd

dd

Remote

Condenser

Located ABOVE

Ice Machine

Remote

Condenser

Located BELOW

Ice Machine

Condenser Distance &

Location Schematic

Max 35’

Max 15’