English-8, Power alarm – Delta Electronics AC Drive VFD-F Series User Manual
Page 8

English-8
20 HP to 40 HP (VFD150F23A, VFD185F23A/43A, VFD220F23A/43A, VFD300F43A)
W/T3
V/T2
3
IM
POWER
S/L2
R/L1
-
( )
( )
+
DC DC
T/L3 +1
-
+2
MOTOR
50 HP to 60 HP (VFD370F43A, VFD450F43A)
R/L1
+1
+2
-
S/L2 T/L3
U/T1 V/T2 2/T3
POWER
IM
MOTOR
3
POWER
ALARM
CHARGE
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG
Power Terminal
Torque: 30Kgf-cm (26 in-lbf)
Wire: 8-2 AWG
Wire Type: Stranded copper only, 75° C
NOTE: If wiring of the terminal utilizes the wire
with a 1AWG-diameter, it is thus necessary to use
the Recognized Ring Terminal to conduct a
proper wiring.
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG
Power Terminal
Torque: 57kgf-cm (49.5 in-lbf) min.
Wire Gauge: VFD370F43A: 3AWG
VFD450F43A: 2AWG
Wire Type: Stranded copper only, 75° C