Install transformer, Install solenoid valve – Sloan ETF-500 Faucet User Manual

Page 4

Advertising
background image

4

3/8” (10 mm)

SUPPLY TUBE

4

Install Transformer

Multiple Faucets
Multiple faucets can be powered by a single transformer that has been
properly sized. Allow a minimum of 15 VA of current rating for each
solenoid valve used. Refer to the following example to determine the
required current rating for 3 OPTIMA faucets.
Example:
Total number of OPTIMA faucets:

3

Total number of solenoid valves:

3

Multiply by current rating:

15 VA
——

Minimum current rating of required transformer: 45 VA

Transformers Available with the ETF-500 and ETF-700 Faucets
Standard Plug-In †

ETF-233

120 VAC

35 VA

Standard Box Mount

EL-248-40

120 VAC

40 VA

† In Canada, use ETF-416 (120 VAC, 35 VA).

Optional Transformers Available from Sloan
Box Mount

EL-154

120 VAC

50 VA

Foot Mount

EL-208

120 VAC

100 VA

Box Mount

EL-342

240 VAC

50 VA

All Sloan transformers are 50/60 Hz.
Other transformers (not supplied by Sloan) may be used, provided they
meet UL requirements for Class 2 transformers.

2

Install Solenoid Valve

A

ETF-500 Faucet Only — Thread Tube Compression Fitting into
inlet hole at bottom of Spout Shank; tighten securely to prevent
leaks.

Note: Flow direction of Solenoid Valve is indicated by arrow on
the Valve Body.

SPOUT SHANK

1/8” (3 mm) NPT
PIPE TO 3/8”
(10 mm) TUBE
COMPRESSION
FITTING

3/8”

COMPRESSION

CONNECTION

COPPER
SUPPLY TUBE

3/8" COPPER

SUPPLY TUBE

(NOT SUPPLIED)

SPOUT

3/8” (10 mm)
COMPRESSION
FITTING

SOLENOID
VALVE

3/8" (10 mm)
BAK-CHEK

®

COMPRESSION
TEE

3/8" COPPER

SUPPLY TUBE

(NOT SUPPLIED)

1/8” (3 mm) NPT
PIPE TO 3/8”
(10 mm) TUBE
COMPRESSION
FITTING

3/8” COPPER
SUPPLY TUBE
(NOT SUPPLIED)

3/8” COPPER

SUPPLY TUBE

(NOT SUPPLIED)

3/8”

COMPRESSION

CONNECTION

SOLENOID
VALVE

3/8” (10 mm)
BAK-CHEK

®

COMPRESSION
TEE

SPOUT

ETF-500

ETF-700

B

All Faucet Models — Connect 3/8 inch O.D. Supply Tube between Compression Connection on outlet side of Solenoid Valve and Compression
Fitting on Spout.

A

ETF-700 Faucet Only —Install the 3/8 inch Straight Compression
Fitting onto the Spout’s copper Supply Tube.

For Dual Line Hot and Cold Water
Supply Applications
Install a 3/8 inch (10 mm) copper supply
tube between Bak-Chek

®

Compression Tee

and hot and cold supply stops. (Supply
stops and copper supply tube furnished by
installer.) Install a 3/8 inch (10 mm) copper
supply tube between Bak-Chek

®

Compression Tee and inlet side of
Solenoid Valve. Tighten
Compression Fittings securely.

Note: Failure to install the Bak-Chek

®

Tee

can result in a cross flow connection
when the faucet is off and the supply
stops are open. If pressure of the hot
and cold water supply differ, hot water
can migrate into the cold water supply or
vice-versa. Most plumbing codes require that
the Bak-Chek

®

be used to prevent this.

3/8” (10 mm)

BAK-CHEK

®

TEE

USED ON DUAL

WATER SUPPLY

APPLICATIONS

ONLY

3/8” (10 mm)

COMPRESSION

FITTING

3/8” (10 mm)

SUPPLY TUBE

SOLENOID

VALVE

SUPPLY

STOP

A

3/8” (10 mm)

COMPRESSION

FITTING

SOLENOID

VALVE

SUPPLY

STOP

B

For Single Line Water Supply Applications
Install a 3/8 inch (10 mm) copper supply tube
between the supply stop and inlet side of
Solenoid Valve. (Supply stop and copper
supply tube furnished by installer.) Tighten
Compression Fittings securely.

Important: Keep thread sealant out of your waterway and prevent
component part damage! Do not use sealant on compression fittings.
When thread sealant is used, do not apply it to the first two “starter”
threads.

Important: Flush dirt, debris, and sediment from the supply line(s).

3

Connect Supply Line(s) from
Supply Stop to Solenoid Valve Inlet

IMPORTANT: Keep thread sealant out of your waterway to prevent
component part damage! DO NOT use any sealant on compression
fittings. For threaded pipe fittings, DO NOT apply sealant to the first
two "starter" threads.