Configuring automatic on battery shutdown – Dell H952N User Manual

Page 51

Advertising
background image

51

Operation

|

Configuring Automatic on Battery Shutdown

If set to Off (default), the load segment turns off only when commanded manually by the

button,

an external command, or through the display (Control > Load Segments).

If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state
activates.

If you select a value, the load segment turns off automatically after the selected delay while the UPS
operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.

To set the shutdown times for each load segment:

1

Press the

button for one second to go to the main menu selection and scroll down to the

Settings menu using the button.

2

Press the

button to enter the Settings menu.

3

Use the button to scroll to the Automatic on Battery Shutdown option and press the

button.

The options display and the current settings flash when selected.

4

Set the shutdown delay for one load segment using the and buttons.

5

Press the

button to confirm.

6

Set the shutdown delay for the other load segment if applicable.

7

Press the

button to confirm.