Air for combustion and ventilation, Installation, Continued – Desa CGCF26TN User Manual

Page 7: Ventilation air, Check gas type

Advertising
background image

111044-01A

For more information, visit www.desatech.com

For more information, visit www.desatech.com

7

7

Figure 6 - Ventilation Air from Outdoors Shown with Optional
Mantel

Outlet
Air

Ventilated
Attic

Outlet
Air

Inlet
Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

AIR FOR COMBUSTION AND
VENTILATION

Continued

Figure 5 - Ventilation Air from Inside Building Shown with
Optional Mantel

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 5). You can also remove door into
adjoining room (see option 3, Figure 5). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation
for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Section 5.3, Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.

IMPORTANT:

Do not provide openings for inlet or outlet air into attic

if attic has a thermostat-controlled power vent. Heated air entering the
attic will activate the power vent.

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

INSTALLATION

Note:

Your Comfort Glow fireplace is designed to be used in zero

clearance installations. Wall or framing material can be placed
directly against any exterior surface of your fireplace, except where
standoff spacers are integrally attached. If standoff spacers are
attached to your fireplace, these spacers can be placed directly
against wall or framing materials.

Use the dimensions shown for rough openings to create the easiest
installation (see Built-In Fireplace Installation, page 9)

CHECK GAS TYPE

Use the correct gas type (natural or propane/LP) for your unit. If
your gas supply is not correct, do not install fireplace. Call dealer
where you bought fireplace for proper type fireplace.

WARNING: A qualified service person must in-

stall fireplace. Follow all local codes.

NOTICE: This heater is intended for use as supple-
mental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this heater as your primary heat source.

AIR FOR COMBUSTION AND VENTILATION

Ventilation Air

INSTALLATION

Check Gas Type

Advertising
This manual is related to the following products: