Super Systems AC20 RS485 Modbus User Manual
Page 39

Page 39/59
TITLE: MODBUS/J-BUS Protocol for SSi’s- AC20 ENG. 824E REV. 1
WORDS FOR DEVICE IN CONFIGURATION MODE - PARAMETERS
“Out.” - Menu Conf. 2 - OUTPUT CONFIGURATION
ADDRESS
(Decimal)
DEC.
Display
R
W
R
Jbus
Mod
Bus
DESCRIPTION
FIGU-
RES
MNEM
CODE
E
A
D
I
T
E
2112
2111
Out 7 function
Range:
0 = Output not used
1 = Linear main control output
2 = Linear secondary control output
3 = Process variable retransmission
4 = Operative set point retransmission
N.A.
(“O7.Fn”)
x
x
2113
2112
Out 7 range
Range:
0 = 0 ÷ 20 mA
1 = 4 ÷ 20 mA
N.A.
(“O7.rn”)
x
x
2114
2113
Retransmission low scale range value for
Out 7
See Mbus
word 300
(“O7.Lr”)
x
x
2115
2114
Retransmission high scale range value
for Out 7
See Mbus
word 300
(“O7.Hr”)
x
x
2116
2115
Time constant for filter on Out 7 analog
retransmission value (in seconds)
0
(“O7.FL”)
x
x