Super Systems 20PQ User Manual
Page 17

13
Switching mode: isolated zero crossing type.
Rated current: from 50 mA to 1 A.
Rated voltage: from 24 V
RMS
to 240 V
RMS
-10 % +15 % (50/
60Hz)
Load type: resistive load only
NOTES 1) To avoid electrical shock, connect power line at
the end of the wiring procedure.
2) For power connections use No 16 AWG or larger
wires rated for at last 75 °C.
3) Use copper conductors only.
4) Don’t run input wires together with power cables.
5) This output is not fuse protected. Please, provide it
externally using a fuse with a I
2
t equal to128.
23
Load
24
Line
26
Load
27
Line
OUT 1
OUT 2
NOTE: This output is not isolated.
A double or reinforced insulation between instrument output and
power supply must be assured by the external solid state relay.
E.3) TRIAC OUTPUTS
Fig. 14 TRIAC OUTPUT WIRING
XKP-1-C2.p65
10/30/01, 9:36 AM
13