Installation – Desa CPVSA18R User Manual

Page 4

Advertising
background image

901273-01D

4

For more information, visit www.desatech.com

For more information, visit www.desatech.com

INSTALLATION

Flue Opening Specifications
Check Gas Type
Venting Specifications for Installation

INSTALLATION

CHECK GAS TYPE

Use only natural gas. If your gas supply is not natural gas, you must
convert the appliance to propane/LP. Follow the instructions on page 7.

If the fireplace does not have a gas supply shutoff valve, one must
be installed.

VENTING SPECIFICATIONS FOR
INSTALLATION

The fireplace chimney flue and vent must be drafting properly. To
check the vent for proper drafting: Light a tightly rolled newspaper
on one end and place it at the inside front edge of the fireplace.
Observe the smoke and be sure the vent is properly drawing it up the
chimney. If the smoke spills out into the room, extinguish the flame
and remove any obstruction until proper venting is achieved.

The chimney flue damper must be fixed open to provide a minimum
of 81 sq. in. of free air opening during operation of this log set. A
multipurpose damper clamp is provided to fix the damper in position.

The minimum flue sizes shown in Figure 2 are based on a 6'
chimney height using round pipe. Your minimum flue size will
vary based on input rate and chimney height. Refer to the National
Fuel Gas Code ANSI Z223.1/NFPA 54, Section 6.6
, for details.

CAUTION: Do not remove the data plates at-

tached to the burner pan. The data plates contain
important warranty and safety information.

WARNING: Before installing in a solid fuel burning

fireplace, the chimney flue and firebox must be cleaned
of soot, creosote, ashes and loose paint by a qualified
chimney cleaner. Creosote will ignite if highly heated.
A dirty chimney flue may create and distribute soot
within the house. Inspect chimney flue for damage.

NOTICE: Installation, service, and repair of this appli-
ance must be performed by a qualified installer,
service agency, company or gas supplier experi-
enced with this type of gas appliance. Only factory
authorized components listed in these instructions
may be used in accordance with the manufacturer’s
instructions and all codes and requirements of the
authority having jurisdiction. Any modifications to
this kit, or use of unauthorized components or acces-
sory items will void the manufacturer’s warranty, and
may result in a hazardous condition.

FLUE OPENING SPECIFICATIONS

Note:

This vented appliance must be installed only in a solid-fuel

burning fireplace with a working flue and constructed of noncom-
bustible material.

The charts in Figure 2 indicate technical information regarding the
installation of your gas log set. Please make sure that all of the
specifications shown are applicable before installation is attempted.

The fireplace must include a working flue and venting system with
the minimum openings shown in the Figure 2.

Btu Input

Natural

Gas

Btu Input

Propane/LP

Gas

Figure 2 - Technical Information Charts

BURNER ORIFICE

LOG

NATURAL

PROPANE/LP

SIZE

IN.

NUM.

COLOR

IN.

NUM. COLOR

18" SA/DA .129

30

Green

.073

49

Red

24" SA

.141

28

Yellow

.086

44

Orange

24" DA

.136

29 White/Yellow .086

44

Orange

30" SA/DA .157

22

Yellow/Blue

.089

43

Black

FUEL PRESSURE

SPECIFICATIONS (W.C.)

Inlet

Manifold*

NG

5.5"-10.5"

3.5"

LP

11"-13"

10"

* ± .2"

DESCRIPTION

18" Single Burner

50,000

40,000

24" Single Burner

60,000

50,000

18" Dual Burner

55,000

45,000

24" Dual Burner

65,000

55,000

30" Dual Burner

70,000

60,000

MINIMUM FIREBOX SIZES

LOG

FRONT

BACK

MINIMUM

SIZE

WIDTH WIDTH*

DEPTH HEIGHT FLUE SIZE

18"

34"

16"

14"

18"

8" dia.

24"

35

3

/

4

"

17"

15

1

/

2

"

18"

8" dia.

30"

42"

27"

18"

18"

9" dia.

*At depth indicated

WARNING: The Massachusetts State Board re-

quires all installations be performed by a Licensed
Plumber or Gas Fitter. Massachusetts state code re-
quires all vent dampers be welded open or removed.