1.7

Turn  on  power  supply  to  the  controller  (and  power  supply  to  the  TE  device  if  applicable),  and  set  tuning 
parameters as necessary.  Controller tuning is discussed in section 3. 

 

Do  not  mount  the  controller  to  a  surface  which  is  exposed  to  a  source  of  heat,  such  as  from 
electronics, machinery, or solar radiation. 

Do not cover the controller with any object or otherwise restrict natural convection airflow around 
the controller. Doing so could cause the controller to overheat. 

Do  not  mount  the  controller  to  an  insulating  surface.  Doing  so  could  cause  the  controller  to 
overheat. 

Do not operate the controller in such a manner as to cause the surface temperature of the circuit 
board or its frame to reach 70 °C. Otherwise the controller might be damaged and there might be a 
risk of fire as a result. 

Do not allow the controller to be exposed to water (such as from dripping or leaking water lines or 
from water‐vapor condensation if the surface temperature of the controller is below the dew point 
temperature). 

Do not allow metallic dust/shavings to contact the controller electronics. 

 

2.0 Control Function Description  

2.1

Proportional  control:    This  eliminates  much  of  the  temperature  cycling  inherent  in  on/off  control.    The 
proportioning bandwidth is the temperature span over which the power is proportioned from 0% to 100% 
power, centered about the temperature set point.  That is, the controller output decreases to 50% power as 
it reaches the set point and to 0% as it reaches the end of the bandwidth range above the set point. 

For example, suppose the controller is being operated in the cooling mode, the set point is 10.0 °C, and the 
bandwidth is set to 5 °C.  The controller power starts to proportionally decrease as the sensor temperature 
cools below 12.5°C.  The power will be reduced to 50% when the sensor is at 10.0 °C.  Finally, the power will 
be  at  0%  when  the  sensor  is  at  7.5°C.    (Of  course,  this  example  presumes  that  the  cooler  would  have 
enough capacity to cool to 7.5 °C.) 

If the bandwidth is set too narrow, the temperature will oscillate around the set point.  If the bandwidth is 
too wide, the controller will be slow to respond or may never reach set point. 

2.2

Integral Control:  This corrects for any offset between the set temperature and the sense temperature by 
averaging the offset with respect to time.  This essentially shifts the proportioning bandwidth. 

For example, suppose the set temperature is 10.0 °C, the bandwidth is set to 5 °C, and the controller settled 
to a constant 11.2 °C (corresponding to 74% power).  If the integral control is set to 1 repeat per minute, 
the controller will increase the power to 98% in 1 minute.  In this example, after one minute of operation 
the  controller  calculated  that  the  error  from  the  desired  temperature  to  actual  temperature  was  +1.2  °C 
above set point.  With a bandwidth of 5 °C, the controller then calculated that it needed an additional 24% 
output  (100% output /  5  °C *  1.2 °C  = 24 %).    This  additional  24%  output  was  added  to  the  existing 74% 
output to yield 98% output.  The integral portion of the output is recalculated at the frequency specified by 
the  integral  potentiometer.    Thus,  at  the  next  update  period  for  the  integral  the  controller  will  add  or 
subtract  as  necessary  from  the  98%  output.    Of  course,  the  maximum  output  is  limited  to  100%  and  the 
minimum is limited to 0%. 

If the integral control is set too high, the temperature will oscillate.  If integral control is set too low, it will 
take a long time for the temperature to settle to steady state. 