101U/R Automatic operation
•
Set the
Auto/Manual switch to Auto.
For all auto and remote control operations, the drive is supplied with a 15 pin D connector.
Never apply mains voltage across any pins on the 15D so cket. Up to 30V may be applied across
pins 2 and 10, but no voltage should be applied across other pins except where specified.
Permanent damage not covered by warranty may result in both instances.
The pump is controllable by an analogue pr ocess signal of up to 30V or 32mA. The pump will provide an increasing
flow rate for rising control signal (
non
-
inverted response
) or an inc reasing flow rate for falling control signal (
inverted
response
).
•
Signal offset is the process signal level which has to be reached in order for the pump rotor to start rotating.
•
Signal range is the change in process signal level necessary to produce the required change in pump rotor speed.
For example, when using a 4mA to 20mA process signal:
Pump response
Signal offset
Signal range
Non-Inverted
4mA
16mA
Inverted
20mA
16mA
For voltage m odes, a s table variable DC voltage s ource c an be us ed in c onjunction with a DC voltmeter, (maximum
30V DC). Polarity set for a non-inverted response. Reverse polarity for an inverted response.
Voltage signal
Input impedance 220 kohms
Response
Range V
Offset V
Pin 10
Pin 2
Non-inverted
5 to 30
0 to 30
-
+
Inverted
5 to 30
0 to 30
+
-
For current modes, the s ame DC s ource can be us ed in c onjunction with a DC m illiampere meter, (maximum 32mA).
Polarity set for a non-inverted response. Reverse polarity for an inverted response.
Current signal
Input impedance 250 ohms
Response
Range mA
Offset mA
Pin 10
Pin 2
Link
Non-inverted
12 to 30
0 to 30
-
+
1&10
Inverted
12 to 30
0 to 30
+
-
1&10