101U/R Automatic operation

Set the

Auto/Manual switch to Auto.

For all auto and remote control operations, the drive is supplied with a 15 pin D connector.

Never apply mains voltage across any pins on the 15D so cket. Up to 30V may be applied across

pins 2 and 10, but no voltage should be applied across other pins except where specified.

Permanent damage not covered by warranty may result in both instances.

The pump is controllable by an analogue pr ocess signal of up to 30V or 32mA. The pump will provide an increasing

flow rate for rising control signal (

non

-

inverted response

) or an inc reasing flow rate for falling control signal (

inverted

response

).

Signal offset is the process signal level which has to be reached in order for the pump rotor to start rotating.

Signal range is the change in process signal level necessary to produce the required change in pump rotor speed.

For example, when using a 4mA to 20mA process signal:

Pump response

Signal offset

Signal range

Non-Inverted

4mA

16mA

Inverted

20mA

16mA

For voltage m odes, a s table variable DC voltage s ource c an be us ed in c onjunction with a DC voltmeter, (maximum

30V DC). Polarity set for a non-inverted response. Reverse polarity for an inverted response.
Voltage signal
Input impedance 220 kohms

Response

Range V

Offset V

Pin 10

Pin 2

Non-inverted

5 to 30

0 to 30

-

+

Inverted

5 to 30

0 to 30

+

-

For current modes, the s ame DC s ource can be us ed in c onjunction with a DC m illiampere meter, (maximum 32mA).

Polarity set for a non-inverted response. Reverse polarity for an inverted response.
Current signal
Input impedance 250 ohms

Response

Range mA

Offset mA

Pin 10

Pin 2

Link

Non-inverted

12 to 30

0 to 30

-

+

1&10

Inverted

12 to 30

0 to 30

+

-

1&10