2 the microprocessor controller, 3 controller display – AEC Econo-Cool Chillers User Manual

Page 32

Advertising
background image

AEC Water Temperature Control Units

Page 31

Pressure Switch

A pressure switch built into each unit keeps the system from starting until the water
supply is turned

On

and subjected to the minimum water supply pressure. This feature

protects the pump seal and the heater from damage through attempted operation
without water. The pressure switch is set at approximately 16 psig (110.32 kPa/1.10
bars) for 250°F (121ºC) units or 55 psig (379.23 kPa/3.79 bars) for 300°F (149ºC) units
prior to leaving the factory.


4-2 The Microprocessor Controller

The controller is an easy-to-operate microprocessor-based PID control device. When
the process reaches the set point, the PID control cycles the cooling valve and/or
immersion heater to maintain the proper leaving water temperature.

The controller has been fully factory tested. Set the desired process
temperature set
point and the
control does the
rest.

Built-in range of
operation on the
controller is 0°F to
250°F (-18ºC to
121ºC).


4-3 Controller

Display

Figure 6

PV or Process Value Numeric LED

During normal
operation, the large
red

PV

Process

Value LED on the
controller displays the actual process temperature at the To Process
thermocouple. It also lists parameter symbols during setup and
error messages if an error occurs.

Figure 6

Typical E5CK Microprocessor Controller

PV

SV

OUT1

OUT2 MANU STOP RMT

AT

SUB1

AT

E5CK