Liebert hybrid advantage models, Nominal voltage codes, Specif ying the appropriate model – Emerson Liebert Surge and Signal Protection User Manual

Page 3: At a glance

Advertising
background image

Model

Configuration

Surge Current Capability (kAmps)

Dimensions* (inches)

Phase

L-G

L-L

L-N

N-G

H x W x D

H1/H2xxxS111

Split Single Phase

250

125

125

125

20 x 16 x 9

3 wire and ground

H1/H2xxxY111

Three Phase Wye

250

125

125

125

20 x 16 x 9

H1/H2xxxD110

Three Phase Delta

250

125

125

20 x 16 x 9

3 wire and ground

H1/H2xxxH111

Three Phase Delta

250

125

125

125

20 x 16 x 9

Hi-Leg, 4 wire and ground

H1/H2xxxS222

Split Single Phase

320

160

160

160

24 x 20 x 9

3 wire and ground

H1/H2xxxY222

Three Phase Wye

320

160

160

160

24 x 20 x 9

4 wire and ground

H1/H2xxxD220

Three Phase Delta

320

160

160

24 x 20 x 9

3 wire and ground

H1/H2xxxH222

Three Phase Delta

320

160

160

160

24 x 20 x 9

Hi-Leg 4 wire and ground

Split Single Phase, 3 Wire plus Ground

120/240

Three Phase Wye, 4 Wire plus Ground

120/208, 230/400, 277/480

Three Phase Delta, 3 Wire plus Ground

208, 240, 400, 480

Three Phase Delta Hi-Leg, 4 Wire plus Ground

120/240

At a Glance

Unique "Surge Current Transition

Circuit" allows for seamless

transition from primary (SAD

technology) to secondary

(MOV array technology)

suppression system. A true,

shared suppression system.

Industry’s only Active Disconnect

System protects against system

failure and degradation due to

overvoltages.

Lowest UL 1449 clamping voltages

achieved—330VAC line to neutral

for a 120/208V Wye unit.

Technology of choice for speed,

allowing picosecond response time.

All surge suppression components

used are computer tested and

matched. SAD’s are matched to +/-

1% and MOVs are matched to 1 volt

for optimum reliability and long life.

Matched low impedance buss

system for both SAD and MOV

modules.

Liebert Hybrid Advantage builds

upon industry standard

Interceptor® Series design. Unique

benefits include:

— Patented component level

monitoring — including neutral

to ground.

— Unique sand-packed silver fuse

network UL Rated at 300kAIC

for safety.

— Highest surge current capability

and survivability in the industry.

— 10-year warranty on parts and

5-year on-site labor, backed by

Emerson Power Service.

3

Liebert Hybrid Advantage Models

Medium Exposure Units

(250kAmp and 320kAmp current capacity units)

Nominal Voltage Codes

(substitute for xxx to complete model number)

Note: For other voltage configurations not listed, please consult factory.

The Liebert Hybrid Advantage features

the fast response time of the Silicone

Avalanche Diode (SAD).

SAD Surge Energy

1

250J

2 500J

L-N Voltage

120 120V

208 208V

230 230V

240 240V

277 277V

480 480V

Configuration

N

Single Phase L-N

L

Single Phase L-L

S

Split Phase

Y

3 Phase Wye

D

3 Phase Delta

H

3 Phase Hi-Leg

Monitoring Options

01

LED

04 LED,

Alarm

05

LED, Surge

Counter

06 LED,

Alarm,

Surge Counter

03

LED, Alarm, Dual

Surge Counters

Connection Type

“blank”

Compression

Lugs

R

Rotary

Disconnect

Specif ying The Appropriate Model

All model numbers begin with a prefix. Use Chart A to build your Liebert Hybrid

Advantage starting with the SAD Surge Energy column. Moving left to right, choose the

correct configuration from each column for your application. Your completed model

number should look similar to the example below:

Example Part Number:

H 2 1 2 0 Y 4 4 4 R - 0 3

Chart A

Surge Current Rating

111

250kA Per Phase

222

320kA Per Phase

333

400kA Per Phase

444

750kA Per Phase

Model

Configuration

Surge Current Capability (kAmps)

Dimensions* (inches)

Phase

L-G

L-L

L-N

N-G

H x W x D

H1/H2xxxS333

Split Single Phase

400

200

200

200

24 x 24 x 9

3 wire and ground

H1/H2xxxY333

Three Phase Wye

400

200

200

200

24 x 24 x 9

4 wire and ground

H1/H2xxxD330

Three Phase Delta

400

200

200

24 x 24 x 9

4 wire and ground

H1/H2xxxH333

Three Phase Delta

400

200

200

200

24 x 24 x 9

Hi-Leg, 4 wire and ground

H1/H2xxxS444

Split Single Phase

750

375

375

375

30x 24 x 9

3 wire and ground

H1/H2xxxY444

Three Phase Wye

750

375

375

375

30x 24 x 9

4 wire and ground

H1/H2xxxD440

Three Phase Delta

750

375

375

30x 24 x 9

3 wire and ground

H1/H2xxxH444

Three Phase Delta

750

375

375

375

30x 24 x 9

Hi-Leg 4 wire and ground

High Exposure Units

(400kAmp and 750kAmp current capacity units)

*Optional Disconnect Doesn’t Change Dimensions