C – horizontal venting – general – Enerco MHU 45 User Manual

Page 6

Advertising
background image

6

Enerco | Compact Unit Heater

Operating Instructions and Owner’s Manual

B – VERTICAL VENTS USING METAL VENT PIPE
– COMMERCIAL AND RESIDENTIAL
INSTALLATIONS

MHU/HSU compact unit heaters are listed as Category I
appliances for vertical vent installations.

1.

MHU/HSU unit heaters are to be used with NFPA- or ANSI-

approved chimneys, U.L. listed type B-1 gas vents, single wall
metal pipe, or listed chimney lining system for gas venting
where applicable, as well as the modifications and limitations
listed in figure 2 . Seal single wall vent material according to
the section A - General Recommendations and Requirements.

2.

The vent connector shall be 3" (76 mm) diameter on 45 unit

and 4” (100mm) diameter for the 75 unit. In all cases, a
flue transition piece (supplied) is required to fit over the

outlet of the induced


draft assembly on the appliance.

3.

Keep the vent connector runs as short as possible with a

minimum number of elbows. Refer to the (American)
National Fuel Gas Code ANSI Z223.1 or (Canada) CSA B149.1
Natural Gas and Propane Installation Code for maximum vent
and vent connector lengths. Horizontal run of the vent
connector from the induced draft blower to the chimney/vent
cannot exceed the values in table 2 .

4.

When the length of a single wall vent, including elbows,

exceeds 5 feet (1.5m), the vent shall be insulated along its
entire length with a minimum of 1/2" thick foil faced
fiberglass 1-1/2# density insulation. If a single wall vent is
used in an unheated area it shall be insulated. Failure to do
so will result in condensation of flue gases.

5.

The unit may be vented vertically as a single appliance or as a

common vent with other gas-fired appliances. In common
venting situations, vent connectors for other appliances must
maintain a 4" (100mm) vertical separation between the vent
connectors. Refer to common venting tables in the(American)
National Fuel Gas Code ANSI Z223.1 or (Canada) CSA B149.1
Natural Gas and Propane Installation Code for proper vent
size.

6.

Clearance to combustible material is 6" (152mm) for single

wall vent material except where a listed clearance thimble
is used. Clearance to combustible material for type B-1 vent or
factory-built chimney is per manufacturer’s instructions.

7.

The vent connector shall be supported without any dips or

sags. Vertical vents shall be supported in accordance with
their listing and manufacturers’ instructions. All horizontal
vent connector runs shall have a slope up to the vertical
vent of at least 1/4" per foot (1mm per 50mm).

8.

All vertical type B-1 vents, single wall vents, or listed chimney

lining system must be terminated with a listed ventcap or
listed roof assembly.

9.

The vent must extend at least 3' (1m) above the highest point

where it passes through a roof of a building and at least 2’
(0.6m) higher than any part of a building within a horizontal
distance of 10' (3.05m) unless otherwise specified by the
(American) National Fuel Gas Code, ANSI Z223.1 or (Canada)

CSA B149.1 Natural Gas and Propane Installation Code.
The vent must extend at least 5' (1.6m) above the highest

connected equipment flue collar.

C – HORIZONTAL VENTING – GENERAL

Common venting is not allowed when horizontally venting the unit
heater.
The minimum horizontal vent length is three feet (914mm).

1.

If possible, do not terminate the horizontal vent through a wall that

is exposed to prevailing wind. Exposure to excessive winds can
affect unit performance. If such a termination is necessary, use a
wind block to protect the vent termination from direct wind.

2.

Vent termination must be free from obstructions and at least

12" (306mm) above grade level and maximum snow height.

3.

Do not terminate vent directly below roof eaves or above a

walkway, or any other area where condensate dripping may
be troublesome and may cause some staining. Avoid windows
where steam may cause fogging or ice buildup.

4.

When horizontally vented, minimum clearance for termination

from any door, window, gravity air inlet, gas or electric meter,
regulators, and relief equipment is 4 ft. (1.2m) for U.S.
installations. Refer to NFPA 54/ANSI Z223.1 in the U.S.A. and
CSA B149.1 Natural Gas and Propane Installation Code
in Canada or with authorities having local jurisdiction. In
Canada, vent termination must have a minimum 6 ft.
(1.8mm) horizontal clearance from gas and electric meters
and relief devices as specified in the CSA B149.1, Natural
Gas and Propane Installation Code.

VENT TERMINATION ON SINGLE WALL VENT

SINGLE WALL TERMINATION

DOUBLE WALL (TYPE B-1) TERMINATION

ROOF FLASHING

ROOF PITCHED

FROM 0” TO 45”

SHALL NOT BE A

CONCEALED SPACE

2” CLEARANCE

THIMBLE

ROOF FLASHING

ROOF PITCHED

FROM 0” TO 45”

12” MAX

CLEARANCE TO BE AS

SPECIFIED ON TYPE “B”

VENT PIPE

SEAL JOINT BETWEEN SINGLE WALL VENT

AND “B”VENT AND THE ANNULAR SPACE OF THE “B” VENT

FIGURE 2

Advertising