Power supply, Power injector, Grounding and lightning protection – H3C Technologies H3C WA2600 Series WLAN Access Points User Manual

Page 12

Advertising
background image

7

Power supply

The AP can be powered by a power injector or through PoE+.

Power injector

You can use an H3C POE5 power injector to power the AP. For more information about how to power

the AP through the power injector, see “

Connecting the AP to a power injector

.”

NOTE:

The power injector is not shipped with the AP and must be ordered separately.

PoE+

If the switch connected to the AP is PoE+ capable, the AP can be powered by the switch through the cable

between the 10/100/1000BASE-TX port of the AP and the Ethernet port of the switch.

Grounding and lightning protection

Table 6 Grounding and lightning protection requirements

Item Requirements

Grounding resistance

•

The grounding resistance is usually required to be less than 5 ohms, and less than

10 ohms in an area with less than 20 thunderstorm days a year. If a piece of angle
steel is buried as the grounding conductor, the grounding resistance is required to

be less than 10 ohms. In an area with a higher grounding resistance, reduce the

grounding resistance by using brine or resistance reducing agent around the

grounding conductor.

•

The top of the grounding conductor should be at least 0.7 m (2.30 ft) away from the
ground surface. In cold areas, the grounding conductor should be buried below

the frozen soil layer.

Grounding
connection

•

If a grounding strip is available, connect the yellow and green grounding cable of

the AP to the grounding strip. To make a grounding cable, make sure the cable is

with a cross-section area of at least 6 mm

2

(0.01 in

2

) and a length of no longer than

3 m (9.84 ft).

•

If no grounding strip is available, bury a piece of angle steel/steel tube at least 0.5
m (1.64 ft) long in the earth to serve as the grounding conductor. In the case of a
piece of angle steel, the size should be at least 50 × 50 × 5 mm (1.97. × 1.97 ×

0.20 in); in the case of a piece of steel tube, it must be zinc-plated and have a wall

thickness of at least 3.5 mm (0.14 in). Weld the yellow and green grounding cable

of the AP onto the grounding conductor and use anti-erosion treatment on the
welding joint. The grounding cable should be as short as possible and must not be

coiled.

•

Make sure that the grounding terminals of all the lightning arresters of the AP and
the peer device of the AP are well grounded.

Grounding lead-in

A grounding lead-in is a metal conductor connecting a grounding net and a
grounding strip. The grounding cable of the AP should be connected to the grounding

strip. The grounding lead-in must be 30 m (98.43 ft) or shorter. A piece of zinc-coated
flat steel with a cross-section area of 40 × 4 mm (1.57 × 0.16 in) or 50 × 5 mm (1.97

× 0.20 in) is recommended. Connect the grounding strip and the grounding lead-in of

the AP through the yellow and green grounding cable with an area of 35 mm

2

(0.05

in

2

), or weld them directly. Use anti-erosion treatment on the welding joint.