Gecko Frames Instruction Manual

47

Video Frame

The conditions monitored by SMPTE Alarm reporting are:

•

Frame Health

•

Power supply 1 voltage

•

Power supply 2 voltage

•

Fan rotation

•

Frame temperature

•

Module Health (capability module dependent, refer to specific module
instruction manual).

•

Power supply voltage

•

Signal present at input

•

EQ warning

•

EDH Monitoring (capability module dependent, refer to specific
module instruction manual).

•

EDH error detected

The impedance between the center conductor and shield of J101 can be in
one of two states:

•

Open – less than100 μA of current will flow, and

•

Closed – less than 2 V will appear from center conductor to shield with
less than 20 mA of current flowing.

There are three operational conditions (capability is module dependent,
refer to specific module instruction manual):

•

Open – no faults,

•

Closed – there is an internal fault, and

•

Pulsing – there has been a signal error detected in one of the modules.

In addition to fault reporting through the SMPTE Alarm connector, there is
a RED Fault LED on the Frame Monitor and 8900NET Network Interface
modules that is visible through the Fault window of the 8900TF/TFN front
cover. This LED is OFF when no fault conditions are detected and ON when
either an internal fault or a signal error is detected.

A number of frames can be coupled together as one alarm circuit by using
a T-connector. Refer to

Figure 21 on page 48

for a typical alarm circuit inter-

connect diagram.