5

www.powerware.com 1.800.356.5794

Technical specifications

General

User interface

Graphical LCD with blue backlight and text in English,

French, German, Portuguese, Italian and Spanish

LEDs

Four status-indicating LEDs

Topology

Double-conversion

Diagnostics

Full system self-test

UPS bypass

Automatic bypass

Dimensions

See model selection guide

Rail kit

Included with all units

Electrical input

Nominal voltage 208V, 230V

200V, 208V, 220V, 230V, 240V and 250V

user-selectable

Voltage range

156–280 Vac (output PF 0.7)

Power draw of

5000 VA: 24.0A @208V

UPS (full load)

6000 VA: 28.8A @208V

Recommended

35A

input breaker
rating

Frequency

50/60 Hz autoselect

Frequency range 40–70 Hz

Electrical output

Power factor

0.7

On utility voltage ±2% of nominal
regulation

On battery

±2% of nominal

voltage regulation

Efficiency

>97% in high-efficiency mode; 91% in normal mode

Frequency

±3% Hz online

regulation

Load crest

3 to 1

factor

Battery

Internal battery

5.5 Ah, sealed, lead-acid; maintenance free

type

External battery

Up to four per 9135, rail kits included for

modules

rack mounting

EBM battery type 5.5 Ah, sealed, lead-acid; maintenance free

Battery runtime

Four (4) minutes with internal batteries @100%

load

(0.7

PF)

For additional details, see battery runtime chart

Battery recharge Six (6) hours to recover 90 percent of nominal backup
time

time after 100 percent RCD load discharge

Battery

Hot-swappable internal and external batteries

replacement

Start-on-battery

Allows start of UPS without utility input

Communications

Serial port

RS-232 as standard, RS-232 cable provided

USB port

As standard (HID)

Relay output

DB-9 Dry Contact—common alarm as standard

Communications Optional communication slots (Mini X-Slot)
slot

Software

LanSafe UPS monitoring and management software

Environmental

Safety markings 208V: UL, NOM, NYCE

230V: CE, C-Tick, UL, GS

EMC markings

208/230V: FCC-A, VCCI-A, BSMI-A, C-Tick,

CE

Compliance

Audible noise

Max 46 dB

Ambient

0˚C (32˚F) to +40˚C (104˚F)

operating

Storage

-20˚C (-4˚F) to +40˚C (104˚F) with batteries and

temperature

-25˚C (-13˚F) to +55˚C

(131˚F)

without

batteries

Relative humidity 5–90% non-condensing

Heat dissipation (BTUs/hour)

Operating mode

Efficiency

5 kVA

6 kVA

Normal

91%

1150

1350

Battery

86%

1650

1960

High efficiency

97%

370

450

Back panel configurations

Choose from a variety of output receptacle combinations.

Back panel configurations vary by model type.

Hardwired models—230V

Hardwired models—208V

Power-corded models—208V