Eaton Electrical POW-R-COMMAND 1000 User Manual

Page 2

Advertising
background image

2

EATON CORPORATION Cutler-Hammer

Pow-R-Command 1000 LCD Display Instruction Leaflet IL01412010E Effective: June 2006

LCD Programming Procedure

1. Press any key to begin. The Eaton logo will be displayed:

After a few seconds, the firmware version will be displayed:

After a few more seconds, the initial status screen will be displayed:

Press

SEL

to get to the

MAIN MENU

.

2. Login

If user passwords have been created on your system by your distrib-
utor/installer, you will see the following screen. Use

UP/DOWN

to

enter the letters of your password and the

SEL

key to advance to the

next letter. Advance the cursor past the end of the blanks to submit
the password.

If this LCD tool has just been powered up, it will have to download
a database from the PRC1000 controller. You may see the following
screen with the progress indicator:

The database may take up to 10 minutes to download during initial
startup. Afterwards, the

MAIN MENU

will be displayed:

3. Set Date/Time/DST/Location

From the

MAIN MENU

, select

Configure Date/Time

. The follow-

ing menu will be displayed:

FIRMWARE VERSION A1

Aug 25, 2006 11:28A

Group Status:

ON: ABC N

OFF: DEFGHIJKLM OP

Press SEL for menu

Aug 25, 2006 11:28A

User ID:

________

Aug 25, 2006 11:28A

Refreshing Database

Please wait... 57%

Press BACK to quit

MAIN MENU

Command Groups ON/OFF

Panel Status Screen

Configure Groups

Configure Date/Time _

Group Status:

ON: ABC N

OFF: DEFGHIJKLM OP

Use

UP/DOWN

to select

Change Date

. Use

SEL

to move through the

date digits. Use

UP/DOWN

to set the month, day and year, respec-

tively. After setting the year, hit

SEL

one more time. The new values

will be displayed on the PRC1000.

Use

UP/DOWN

to highlight

Change Time

. Use

SEL

to move through

the time digits. Use

UP/DOWN

to set the hour, minute and AM/PM,

respectively. After setting the AM/PM, hit

SEL

one more time.

The new values will be displayed on the PRC1000.

Use

UP/DOWN

to highlight

Change DST

. Use

SEL

to start editing the

DST setting. Use

UP/DOWN

to choose

NONE

,

AUTO

or

MANUAL

. If

MANUAL

is chosen, settings for start and end date will appear. Hit

SEL

to jump to the start date. Use

UP/DOWN

to set the month and day

values. Use

SEL

to move through the digits. After setting the DST

setting (or dates for MANUAL), hit

SEL

one more time. The new

values will be displayed on the PRC1000.

Use

UP/DOWN

to highlight

Change ASTRO-Loc

. Hit

SEL

to start

editing the location. The following screen will be displayed:

Use

UP/DOWN

to set the latitude value in degrees. The latitude range

is -90 (South) to +90 (North).

Note:

Sunrise/sunset calculations lose accuracy outside the -62 to

+62 range. Hit

SEL

to move to the longitude setting. Use

UP/DOWN

to

set the longitude value in degrees. The longitude range is +180
(Alaska) to -180 (Western Pacific). Hit

SEL

to move to the timezone

setting. Use

UP/DOWN

to set the timezone value in hours. The

timezone range is +12 hours (west of GMT) to -12 hours (east of
GMT). After setting the timezone, hit

SEL

one more time. The new

values will be displayed on the PRC1000. The RISE and SET times
will update with the new values calculated from the input latitude and
longitude and the screen will return to the

Configure Date/Time

menu. Use

BACK

to return to the

MAIN MENU

.

4. Configure Breaker Group A

From the

MAIN MENU

, select

Configure Groups

. The following

screen will be displayed:

The group is shown, followed by its current status (

OFF

in this

example). The next line is the group description, if it exists (

GROUP A

LIGHTS

in this example), followed by the number of loads (breakers)

that has been associated with this group (15 in this example).

CONFIGURE DATE/TIME

Change Date__08/23/06

Change Time 11:37 AM

Change DST MANUAL

St: mm/dd End: mm/dd

Change Astro Loc.

ASTRO LAT:

33.00

LON: 84.00

TIMEZONE: 5

RISE 06:30 SET 07:00

SELECT GROUP

TO CONFIGURE:

Group A GRPA OFF

GROUP A LIGHTS

15 loads in group.

Use up/down/sel to

change selection

Advertising