3 guard input, 4 analog output, 5 accuracy - analog models – Emerson Process Management Bristol Series 9110 User Manual

Page 52: 6 accuracy - raise/lower models, 7 dc power, 8 stepper drive mechanism

Advertising
background image

Specifications 6-2

CI-9110

6.3 GUARD INPUT


Enables or inhibits command signal input on both Analog and raise/Lower models.

6.4 ANALOG OUTPUT


Function:

Current feedback signal tracks the output of
the Remote Set Regulator. Signal is typically
used to telemeter pressure output value back
to the command site.


Range:

4 - 20 mA common ground type output


Load Resistance:

380 Ohms Max.

6.5 ACCURACY - ANALOG MODELS


Electrical Input to Pressure Output: ±5% of span

Pressure output to Feedback:

±

5% of span

6.6 ACCURACY - RAISE/LOWER MODELS


Feedback Volts to Pressure Output:

±

5% of span


Pulse Input to Pressure Output:

±

20% of span

6.7 DC POWER


12 Volt Model:

11 - 14 Vdc @ 0.35 A Max.


24 Volt Model:

22 - 28 Vdc @ 0.25 A Max.


Fuse:

1 A, 250 Vdc, 3AG

6.8 STEPPER DRIVE MECHANISM


Stepper Motor:

Gearing from motor shaft to pressure
regulator assembly results in approximately
22,000 incremental steps for 100% output
range travel.


Output Rate of Change:

Full scale sweep adjustable from 1.8 to 69.4
minutes.


Environmental Effects:

±

1.0% Max. full scale per 50°F (28°C)


Supply Voltage Effect:

±

0.15% Max. full scale per 1 volt change