13 decommissioning, 1 disconnecting the ac field plug – SMA SB 240 User Manual

Page 64

Advertising
background image

13 Decommissioning

13.1 Disconnecting the AC Field Plug

Removing and reassembling the AC field plug is only possible within 72 hours

• In total, the AC field plug may at maximum be removed three times and only within the

first 72 hours after the first assembly.

• After the period of 72 hours has expired, the AC field plug must not be removed.
• The cable must be shortened again before the assembling.

Procedure:

1.

Danger to life due to electric shock
Do not disconnect the AC field plug under load.

• Ensure that the circuit breaker is switched off and that it cannot be reconnected.
• Make sure that the PV modules are covered.

2. Unlock and remove the AC field plug from the

connector of the inverter AC cable. Hook a flat-
blade screwdriver (blade width: 4 mm) into the
wide slot at the AC field plug and lever it open.
At the same time, pull out the AC connector.

3. If necessary, disassemble the AC field plug:

• Loosen the screw connection of the plug enclosure.
• Remove the seal from the opening of the thread. Make sure not to damage the fins of the

plug enclosure.

• Detach the plug enclosure from the

insulator. Insert a flat-blade screwdriver
(blade width: 4 mm) into the small slot of
the plug enclosure and unlock the fastening
clamps until the insulator is detached from
the plug enclosure.

• Loosen all three screws using a screwdriver and remove the conductors.
• Prior to reassembling the AC field plug, shorten the cable.
• If necessary, reassemble the AC field plug (see Section 6.4 "Assembling the AC Field

Plug", page 33).

13 Decommissioning

SMA Solar Technology AG

Installation Manual

SMA-SB240-IA-en-12

64