4 specifications – SMA FLX Series Sensor Interface Option User Manual

Page 10

Advertising
background image

4 Specifications

Terminal

Parameter

Parameter Details

Specification

All terminals

Wiring terminal

Maximum wire gauge, solid wire

1.5 mm

2

Maximum wire gauge, stranded

wire

1.0 mm

2

Cabling

Cable jacket diameter (

⌀)

4-8 mm

Temperature sensor input

TEMP MOD

TEMP AMB

TEMP IR.

Sensor input

Sensor type

3 x PT1000

3)

Nominal resistance/temperature

coefficient

3.85

Ω/

o

C

Measurement range

-20

o

C - +100

o

C

Measurement accuracy

±2

o

C

Short-circuit protection

Yes

Electrical safety

Direct contact protection

Double/Reinforced insulation

Cabling

Cable type

Single pair - 2-wire

1)

Maximum resistance per wire

2)

2

Ω

Irradiation sensor input

IR+

IR-

Sensor input

Sensor type

Current shunt (passive)

Measurement range

0 - 150 mV

Max. output impedance (sensor)

500

Ω

Input impedance (electronics)

24 k

Ω

Measurement accuracy

±5 % at 150 mV sensor output

voltage

Short-circuit protection

Yes

Electrical safety

Direct contact protection

Double/Reinforced insulation

Cabling

Cable type

Single pair - 2-wire

1)

Two pairs - 4 wires with temperature

compensation

Maximum resistance per wire

2)

10

Ω

Energy meter input

S0+

S0-

Sensor input

Sensor type

S0 output device

Sensor input class

Class A

Nominal output current

12 mA for an 800

Ω load

Maximum short-circuit output

current

24.5 mA

Open-circuit output voltage

+12 VDC

Maximum pulse frequency

16.7 Hz

Short-circuit protection

Yes

Electrical safety

Direct contact protection

Double/Reinforced insulation

Cabling

Cable type

Single pair - 2-wire

1)

Maximum resistance per wire

2)

10

Ω

Relay output (normally open)

RELAY (NO)

Relay output

Relay type

Potential free contact

Rating AC

250 VAC maximum permitted voltage,

1.0 A, 230 W

Rating DC

24 VDC, 1.0 A, 24 W

Electrical safety

Overvoltage category

Class III

Cabling

Cable type

Single pair - 2-wire

1)

Table 4.1 Sensor Interface Specifications

1)

Shielded or unshielded cables may be used.

2)

Cable resistances will result in a measurement offset.

3)

3

rd

input is used for compensation of the irradiation sensor.

Specifications

L00410607-02_2q / Rev. date: 2014-06-20

9

4

4