Notice – SMA FLX Series PLA Option User Manual
Page 11

2.1.2 Configuring Remotely Controlled
Adjustment of Reactive Output Power
Level
To configure the remotely controlled Power Level
Adjustment, choose the ‘Reactive power’ submenu.
•
Set the ‘Remotely controlled reactive power (Q)’
radio button.
•
Configure the relay states (K1–K6) according to
the requirements of the DNO by entering the
appropriate reactive power setpoint of Q for each
relay state specified by the DNO. The value
entered is set on each inverter and represents the
amount of reactive power that the inverter will
deliver.
•
Leave Q settle time at 10 s, unless otherwise
specified by the DNO.
NOTICE
Q values can also be entered as absolute values by
changing the unit using the drop-down box.
Illustration 2.3 Configuring Reactive Power Control
Setup
10
L00410649-02_2q / Rev. date: 2014-06-20