5 Electrical Connection
SMA Solar Technology AG
20
PCONTROLMOD-IA-en-15
Installation Manual
Functions of Signals D1 to D4 in Operating Mode Remote Shutdown
(Default Settings for Italy)
Pin
Signal
Pin 5 / Pin 14
+ 12 V
Pin 4 / Pin 15
D4
Pin 3 / Pin 16
D3
Pin 2 / Pin 17
D2
Pin 1 / Pin 18
D1
D1
D2
D3*
* The signals D3 and D4 are not evaluated in the operating mode Remote shutdown.
D4*
Function
Closed
Closed
Open/Closed
Open/Closed
No specification
Open
Closed
Open/Closed
Open/Closed
Remote shutdown
Closed
Open
Open/Closed
Open/Closed
Narrowing of
frequency limits
Open
Open
Open/Closed
Open/Closed