6  Electrical Connection

SMA America, LLC

32

CU600-1000US-IA-en-10

Installation Manual

Requirements:

☐ All conduits must be correctly connected to the Connection Unit (see Section 6.3).
☐ The DC switch-disconnector must be turned OFF and the lid of the Connection Unit must be

dismantled.

Procedure:

2. Lead the grounding conductors trough the conduit into the interior of the Connection Unit.
3. Strip the insulation of the grounding conductor

23

⁄

32

in. (18 mm).

4. Connect the grounding conductor to one of the

termination points of the terminal with the symbol

and tighten with a screwdriver (blade width: 6

mm) (torque: at least 44.3 in-lb. (5 Nm)).

5. Ensure that the grounding conductor is firmly positioned.

1.

Danger to life due to electric shock

• Make sure all devices connected to the Connection Unit (e.g inverter) are switched off

and protected against reconnection (see manual of the respective device).

• Ensure that no DC voltage is present.