6 Assembly
SMA Solar Technology AG
18
SCCP-JP-MA-Silence-en-10
Mounting Instructions
Procedure:
1. Position the new rear panel in front of the inverter opening and
ensure that it cannot tip over.
2. Apply metal-free allround paste to the rear-panel bolt for mounting the grounding cable.
3. Fasten the grounding cable to the rear-panel bolt using a suitable
torque wrench (torque: 6 Nm).
4. Ensure that the grounding cable is correctly mounted.
5. Hook the rear panel into the hook fitting.
6. Apply metal-free allround paste to all threads and set screws.
7. Align the rear panel on the inverter.
8. Insert the five upper screws of the rear panel into the threads and
tighten (torque: 8 Nm).
9. Make sure that the rear panel is correctly mounted.