7  Changing the Configuration of the PV Inverters

Installation Manual

FSS-UK-IA-en-20

17

7 Changing the Configuration of the PV Inverters

In battery-backup systems, the active power of the PV inverters should be controllable depending on the frequency (see

the Planning Guidelines "SMA Flexible Storage System with Battery-Backup Function"). If your grid operator prohibits the

reduction of active power feed-in in case of overfrequency, you can also use the PV inverters without changing the

configuration. SMA Solar Technology AG recommends activating the frequency-dependent control of the PV inverters.

Requirements:

☐ The PV inverters are part of a battery-backup system and the automatic transfer switch can disconnect the PV inverters

from the utility grid.

☐ The grid operator must be informed of the configuration change and have no objections to it.
☐ You must be authorized to change Grid Guard parameters. You can find the application form at

www.SMA-Solar.com in the download area of the relevant PV inverter.

☐ The firmware version of the PV inverters must support the frequency-dependent control of active power (for "PV

inverters", see the Planning Guidelines "SMA Flexible Storage System with Battery-Backup Function" at

www.SMA-Solar.com).

Procedure:

1. With existing PV systems, make sure that the firmware of the installed PV inverters supports frequency-dependent

active power reduction (see the Planning Guidelines "SMA Flexible Storage System with Battery-Backup Function"

at www.SMA-Solar.com).

2. Set the following parameters of the PV inverters to the specified value (see the documentation of the communication

product).

Parameter

Value

P-WCtlHzMod
Operating mode of active power reduction in case of overfrequency P(f)*

* Menu Equipment & device control system

On or WCtlHz

P-WGra
Active power gradient, linear instantaneous power gradient configuration*

40

P-HzStr
Difference between starting frequency and grid frequency, linear instantaneous power

gradient configuration*

0.2

P-HzStop
Difference between reset frequency and grid frequency, linear instantaneous power gradient

configuration*

0.2

P-HzStopWGra
Active power gradient after reset frequency, linear instantaneous power gradient

configuration*

10