If necessary, tighten the screw terminal to the busbar again using a torque wrench with a torque of
27 ft‒lb. (37 Nm).
Connecting AC cables to busbars with cable lugs
Figure 42: Connection of AC cables to busbar with copper cable lug
Position
Description
A
Screw head - size: M 12
B
Spring washer
C
Washer
D
Cable lug
E
Busbar
F
Nut - size: M 12
E
D
B C
A
F
C B
A
B C
B
F
C