Installation Guide
5.7 Multi-function relay connection
5.7.1 Connection Requirements
You have the possibility to use an external signal transmitter to display smooth operations as well as
errors.
You can switch the following voltages and currents.
Cable Requirements
• Use cables of type 600V LVLE.
• The cable type and cable-laying method must be appropriate to the application and location.
• The cable must be double-insulated.
Maximum voltage
Maximum current
AC source
15 V
1.0 A
DC source
30 V
1.0 A
Item
Description
Value
A
External diameter
15
⁄
32
in. …
1
⁄
2
in.
(11.7 mm ... 12.5 mm)
B
Cross-section of insulated conductor
AWG 20 … AWG 14
0.5 mm² ... 2.5 mm²
C
Maximum length of the insulated
conductor
1
⁄
2
in. (15 mm)
D
Maximum strip insulation
3
⁄
8
in. (8 mm)