Active Power Limitation
SMA Solar Technology AG
56
SC-BEN100262
User Manual
Procedure "WCnstNomAnIn"
If you have selected the procedure "WCnstNomAnIn", you must connect a signal to the analog input
"ExtSolP" of the Sunny Central. The strength of the connected signal current determines the nominal
active power in percent.
Current
Nominal active power
4 mA
0 %
8.5 mA
30 %
11.5 mA
50 %
13 mA
60 %
19 mA
100 %